GT UPS
  • pl
  • ua

UPS GT S Rack/Tower 10kVA On-Line 1F

UPS GT S Rack/Tower 10kVA On-Line 1F

UPS GTS 10000 RT2U

 

  • ON-LINE technology (double conversion)
  • VFI with frequency controller feature
  • avaliable with generator connection
  • hight Power Factor = 0,9
  • USB, RS232 installed & Dry Contacts DB9 in chosen models
  • as an option – remote control cards (SNMP, AS400, relay card)
  • additional battery packs avaliable
  • „Cold Start” feature
  • service by-pass with protection and voltage stabilizer
  • built-in control panel with LCD display
  • EPO (e.g. for fire system)

Zapytanie

Technical specifications

Power

10000VA / 9000W

INPUT
Voltage rate

120V – 276V

Frequency rate

45Hz – 55Hz, 54Hz – 66Hz

tdDi

<5%

Input connector

 terminal block

Connector for battery module    

Yes

Output
Voltage

208V, 220V, 230V, 240V

Frequency (line mode)

45Hz – 55Hz, 54Hz – 66Hz

Frequency (battery mode.)

50Hz / 60Hz – ±0,2Hz

Power Factor (PF)

0,9

Peak factor

3:1

Waveform

Sinusoida

Output connector

IEC C19(8pcs)

EFFICIENCY
Line mode

>93%

ECO mode

>97%

Battery
Backup time*

6 min

Charging time

3h do 90%

 

 

TRANSFER TIME
linear ↔ battery

0ms

inverter ↔ bypass    

0ms

inverter → eco

1ms

eco → inverter

<10ms

INTERFACE
Display

LCD

Communication port

EPO, RS-232, Voltage-free contacts, USB

Slot for expansion cards

AS400, relay card, SNMP

Software

Compaq, Free BSD, HP-UX, IBM Aiz, Linux, MAC, SGI IRIX, SunSolaris, True64, Windows

PHISICAL
Dimensions

438 x 215 x 704

Weight with batteries

82kg

OTHER
Noise level

<55dB

Operating temperature

0°C – 40°C

Audiable alarms

Tak

* backup time at PF=0.7 and 75% load. For you calculation needs please contact our Sales Department. We’ve made an effort to provide correct technical data in this publication but we recommend to contact our Sales Department in case of any doubts before making your purchase decisions. Any errors in the description do not constitute grounds for a claim.

To download