UPS GT MODULAR 75kVA/75kW On-Line 3F/3F
- Power 75 kVA / 75 kW
- Power factor (PF) 1
- Backup time depends on battery configuration
| Power | 75 kVA / 75 kW |
| Topology (IEC 62040-3) | On-line double conversion (VFI-SS-111) |
| Form factor | 3 x 25 kVA modules in 100 kVA frame |
| POWER MODULES | |
| Module power | 25 kVA / 25 kW (hot-swap) |
| Frame (number of slots) | up to 4 modules (100 kVA) |
| Dimensions (W x H x D) | 442 x 86 x 620 mm |
| Weight | 21 kg |
| INPUT | |
| Phases | 3 |
| Nominal voltage | 380 / 400 / 415 V |
| Voltage range | 138–485 V |
| Nominal frequency | 50 / 60 Hz (auto-sensing) |
| Frequency range | 40–70 Hz |
| Input power factor | ≥ 0.99 |
| Current distortion (THDi) | < 3% |
| Input connection | 3P + N + PE (terminal block) |
| Earthing system | TN-S / TN-C / TN-C-S / TT |
| BYPASS | |
| Bypass | separate bypass input |
| Bypass voltage range | -60% / +25% |
| Input connection | 3P + N (terminal block) |
| OUTPUT | |
| Phases | 3 |
| Output voltage | 380 / 400 / 415 V (configurable) |
| Voltage accuracy | ±1% |
| Output frequency | 50 / 60 Hz ±0.1% (battery mode) |
| Power factor (PF) | 1 |
| Crest factor (CF) | 3:1 |
| Voltage distortion (THDu) | ≤ 1% |
| Overload capacity | < 110%: transfer to bypass after 60 min; 110–125%: transfer to bypass after 10 min; 125–150%: transfer to bypass after 1 min; > 150%: transfer to bypass after 200 ms |
| Output connection | 3P + N + PE (terminal block) |
| BATTERIES | |
| Battery technology | VRLA / AGM / Li-ion |
| Battery voltage | 240 V DC (configurable 180–276 V DC) |
| Internal batteries | 30–46 x 12 V in external EBM/STB |
| Backup time* | depends on battery configuration |
| Charging current | 10 A per power module |
| EFFICIENCY AND FUNCTIONS | |
| Efficiency | ≤ 96% |
| Efficiency (ECO mode) | ≤ 99% |
| Transfer time | synchronised transfer: 0 ms |
| Cold start | cold start, soft start |
| Frequency converter mode | yes (CVCF) |
| EPO connector | yes |
| Protections | short-circuit, overload, overtemperature |
| Alarms | overload, battery mode, low battery, fan failure |
| Redundancy | N+X |
| Parallel operation | up to 2 cabinets |
| EMC | PN-EN IEC 62040-2, C3 |
| COMMUNICATION | |
| Control panel | LED + 7" LCD touch screen |
| Menu languages | 12, including Polish |
| Communication ports | USB / RS232 / RS485 / dry contacts / RJ45 / WEB / SNMP / CAN |
| Optional cards | WiFi / GPRS |
| ENCLOSURE AND ENVIRONMENT | |
| Dimensions (W x H x D) | 600 x 1200 x 850 mm |
| Weight | 260 kg (full configuration) |
| Ingress protection | IP20 |
| Colour | black |
| Operating temperature | 0–40 °C |
| Humidity | 0–95% (non-condensing) |
| Operating altitude | up to 1000 m a.s.l. without derating |
| Noise level (1 m) | ≤ 65 dB |
GT MODULAR is a modular three-phase on-line UPS (VFI-SS-111). The cabinet holds up to 4 (100 kVA frame) or up to 8 (200 kVA frame) power modules of 25 kVA / 25 kW. Modules are replaced without powering down the load, and an extra module provides N+1 redundancy.
The modular design reduces upfront cost: buy the capacity you need today and expand as the load of your server room or data center grows.
Yes. Additional 25 kVA modules are inserted into free cabinet slots without powering down the load.
It depends on the number and capacity of batteries in the external cabinets. Our Sales Department will design a configuration for the required runtime.
Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.
Karta Katalogowa V3 GT Modular Tower 25-200kVA.pdf