UPS GT S 11 3kVA/2,7kW On-Line 1F Tower
- Power 3000 VA / 2700 W
- Waveform sine wave
- Power factor (PF) 0.9
| Power | 3000 VA / 2700 W |
| Topology (IEC 62040-3) | On-line double conversion (VFI) |
| Form factor | free-standing Tower |
| INPUT | |
| Phases | 1 |
| Nominal voltage | 220 / 230 / 240 V |
| Voltage range | 100–300 V |
| Nominal frequency | 50 / 60 Hz (auto-sensing) |
| Frequency range | 40–70 Hz |
| Input power factor | ≥ 0.99 |
| Current distortion (THDi) | < 5% |
| Input connection | IEC 60320 C20 (16 A) |
| Earthing system | TN-S / TN-C / TN-C-S / TT |
| Bypass | internal electronic; external manual (optional) |
| OUTPUT | |
| Output voltage | 220 / 230 / 240 V (configurable) |
| Voltage accuracy | ±1% |
| Output frequency | 50 / 60 Hz |
| Waveform | sine wave |
| Power factor (PF) | 0.9 |
| Crest factor (CF) | 3:1 |
| Voltage distortion (THDu) | ≤ 2% |
| Overload capacity (line mode) | 100–105%: continuous; 105–130%: transfer to bypass after 1 min; 130–150%: transfer to bypass after 10 s; > 150%: transfer to bypass after 0.3 s |
| Output sockets | 4 x IEC 60320 C13 + 1 x IEC 60320 C19 |
| BATTERIES | |
| Battery technology | VRLA / AGM |
| Internal batteries | 6 x 12 V / 9 Ah |
| Battery voltage | 72 V DC |
| Backup time* | ≈ 6 min |
| External battery modules (EBM) | yes (optional) |
| Charging current | 1.5 A |
| Recharge time | approx. 3 h to 90% capacity |
| EFFICIENCY AND FUNCTIONS | |
| Efficiency | ≤ 91% |
| Efficiency (ECO mode) | ≤ 98% |
| Transfer time | mains ↔ battery: 0 ms; mains ↔ bypass: 4 ms |
| Cold start | yes |
| Frequency converter mode | yes (CVCF) |
| EPO connector | yes |
| Protections | short-circuit, overvoltage, overload, overtemperature |
| Alarms | overload, battery mode, low battery, fan failure |
| Parallel operation | no |
| EMC | PN-EN IEC 62040-2, C2 |
| COMMUNICATION | |
| Control panel | monochrome LCD display, 4 buttons |
| Menu languages | 8, including Polish |
| Communication ports | USB (HID) / RS232 (DB9) / Intelligent Slot |
| Optional cards | Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts |
| Operating systems | MS Windows / Linux / Unix / MacOS |
| ENCLOSURE AND ENVIRONMENT | |
| Dimensions (W x H x D) | 190 x 327 x 393 mm |
| Weight with batteries | 22.7 kg |
| Ingress protection | IP20 |
| Colour | black |
| Operating temperature | 0–40 °C |
| Humidity | 0–95% (non-condensing) |
| Operating altitude | up to 1000 m a.s.l. without derating; 1000–3000 m: -1% per 100 m |
| Noise level (1 m) | ≤ 40 dB |
* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.
GT S 11 3kVA Tower is an on-line double-conversion (VFI) UPS in a compact free-standing enclosure. The inverter continuously supplies the load with a stable sine wave, so outages, sags and mains disturbances never reach the protected equipment.
The UPS can operate as a frequency converter (CVCF). The wide input voltage range reduces battery use on unstable mains, and EBMs extend the backup time.
For servers and NAS, CAD workstations, laboratory and medical equipment, alarm panels and automation that require a pure sine wave and zero transfer time.
Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.