UPS GT S 11 6kVA/6kW On-Line 1F Tower

  • Power 6000 VA / 6000 W
  • Waveform sine wave
  • Power factor (PF) 1

Request a quote Specifications

UPS GT S 11 6kVA/6kW On-Line 1F Tower

GT S 11 6kVA/6kW Tower UPS – an on-line double-conversion UPS with internal batteries for server rooms, laboratories, security systems and industrial automation.

  • On-line VFI, PF 1 (kW = kVA)
  • Internal batteries, approx. 12–15 min backup*
  • Parallel operation of up to 3 units
  • Up to 95% efficiency, up to 98% in ECO mode
  • USB, RS232, dry contacts, EPO, SNMP/Modbus slot

Size your UPS in the calculator or request a quote.

Zapytanie

Technical specifications

Power

6000 VA / 6000 W

Topology (IEC 62040-3)

On-line double conversion (VFI-SS-111)

Form factor

free-standing Tower

INPUT
Phases

1

Nominal voltage

220 / 230 / 240 V

Voltage range

110–276 V

Nominal frequency

50 / 60 Hz (auto-sensing)

Frequency range

40–70 Hz

Input power factor

≥ 0.99

Current distortion (THDi)

< 3%

Input connection

1P + N + PE (terminal block)

Earthing system

TN-S / TN-C / TN-C-S / TT

Bypass

internal electronic; external manual (optional)

OUTPUT
Output voltage

220 / 230 / 240 V (configurable)

Voltage accuracy

±1%

Output frequency

50 / 60 Hz

Waveform

sine wave

Power factor (PF)

1

Crest factor (CF)

3:1

Voltage distortion (THDu)

≤ 2%

Overload capacity (line mode)

100–105%: continuous; 105–130%: transfer to bypass after 1 min; 130–150%: transfer to bypass after 10 s; > 150%: transfer to bypass after 0.3 s

Output connection

1P + N + PE (terminal block)

BATTERIES
Battery technology

VRLA / AGM

Battery voltage

240 V DC (optionally 192–240 V DC)

Internal batteries

20 x 12 V / 7 Ah or 20 x 12 V / 9 Ah

Backup time*

≈ 12 min (7 Ah) / ≈ 15 min (9 Ah)

External battery modules (EBM)

yes (optional)

Charging current

4 A

Recharge time

approx. 3 h to 90% capacity

EFFICIENCY AND FUNCTIONS
Efficiency

≤ 95%

Efficiency (ECO mode)

≤ 98%

Transfer time

mains ↔ battery: 0 ms; mains ↔ bypass: 4 ms

Cold start

yes

Frequency converter mode

yes (CVCF)

EPO connector

yes

Protections

short-circuit, overvoltage, overload, overtemperature

Alarms

overload, battery mode, low battery, fan failure

Parallel operation

up to 3 units (common or separate batteries)

EMC

PN-EN IEC 62040-2, C3

COMMUNICATION
Control panel

monochrome LCD display

Menu languages

8, including Polish

Communication ports

USB (HID) / RS232 (DB9) / dry contacts / Intelligent Slot

Optional cards

Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts

Operating systems

MS Windows / Linux / Unix / MacOS, VMware ESXi, Hyper-V

ENCLOSURE AND ENVIRONMENT
Dimensions (W x H x D)

220 x 589 x 492 mm

Weight without batteries

13 kg

Ingress protection

IP20

Colour

black

Operating temperature

0–40 °C

Humidity

0–95% (non-condensing)

Operating altitude

up to 1000 m a.s.l. without derating; 1000–3000 m: -1% per 100 m

Noise level (1 m)

≤ 45 dB

* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.

GT S 11 6kVA UPS – overview

GT S 11 6kVA is a single-phase on-line double-conversion UPS (VFI-SS-111) with unity power factor and terminal block connections. Up to three units can be paralleled for more power or N+1 redundancy.

It is suited to server rooms, laboratories, security systems, industrial automation and sites that require long backup times from external batteries.

Frequently asked questions

Can several GT S 11 units be connected in parallel?

Yes, up to 3 units, with common or separate battery sets.

Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.