GT UPS
  • Polski
  • Українська

UPS GT S 11 IoT 2kVA/2kW On-Line 1F Rack/Tower 2U

  • Power 2000 VA / 2000 W
  • Waveform sine wave
  • Power factor (PF) 1

Request a quote Specifications

UPS przód.png

UPS GT S 11 IoT 2kVA/2kW On-Line 1F Rack/Tower 2U

GT S 11 IoT 2kVA/2kW UPS – an on-line double-conversion UPS with unity power factor (VA = W) for 19" rack or tower installation. For servers, switches, storage and automation systems.

  • On-line VFI, PF 1, 0 ms transfer time
  • Approx. 9 min backup time*, expandable with EBMs
  • Hot-swappable batteries
  • Sockets: 8 x IEC C13, in two groups (programmable)
  • IoT RJ45 port, USB, RS232, dry contacts, SNMP/Modbus/WiFi slot

Size your UPS in the calculator or request a quote.

Buy from B2B
1kva Tył.png

UPS GT S 11 IoT 2kVA/2kW On-Line 1F Rack/Tower 2U

GT S 11 IoT 2kVA/2kW UPS – an on-line double-conversion UPS with unity power factor (VA = W) for 19" rack or tower installation. For servers, switches, storage and automation systems.

  • On-line VFI, PF 1, 0 ms transfer time
  • Approx. 9 min backup time*, expandable with EBMs
  • Hot-swappable batteries
  • Sockets: 8 x IEC C13, in two groups (programmable)
  • IoT RJ45 port, USB, RS232, dry contacts, SNMP/Modbus/WiFi slot

Size your UPS in the calculator or request a quote.

Buy from B2B

    Zapytanie

    Technical specifications

    Power

    2000 VA / 2000 W

    Topology (IEC 62040-3)

    On-line double conversion (VFI-SS-313)

    Form factor

    Rack 19" / Tower, 2U

    INPUT
    Phases

    1

    Nominal voltage

    200 / 208 / 220 / 230 / 240 V

    Voltage range

    110–300 V

    Nominal frequency

    50 / 60 Hz (auto-sensing)

    Frequency range

    40–70 Hz

    Input power factor

    ≥ 0.99

    Current distortion (THDi)

    < 3%

    Input connection

    IEC 60320 C20 (16 A)

    Earthing system

    TN-S / TN-C / TN-C-S / TT

    Bypass

    internal electronic; external manual (optional)

    OUTPUT
    Output voltage

    200 / 208 / 220 / 230 / 240 V (configurable)

    Voltage accuracy

    ±1%

    Output frequency

    50 / 60 Hz

    Waveform

    sine wave

    Power factor (PF)

    1

    Crest factor (CF)

    3:1

    Voltage distortion (THDu)

    ≤ 1%

    Overload capacity (line mode)

    100–105%: continuous; 106–125%: transfer to bypass after 5 min; 126–150%: transfer to bypass after 30 s; > 151%: transfer to bypass after 750 ms

    Overload capacity (battery mode)

    100–105%: continuous; 106–125%: shutdown after 3 min; 126–150%: shutdown after 10 s; > 151%: shutdown after 550 ms

    Output sockets

    8 x IEC 60320 C13

    BATTERIES
    Battery technology

    VRLA / AGM

    Internal batteries

    6 x 12 V / 7 Ah

    Battery voltage

    72 V DC

    Backup time*

    ≈ 9 min

    Hot-swappable batteries

    yes

    External battery modules (EBM)

    yes (optional), EBM/STB with auto-detection

    Charging current

    1.8 A

    Recharge time

    approx. 3 h to 90% capacity

    EFFICIENCY AND FUNCTIONS
    Efficiency

    ≤ 93%

    Efficiency (ECO mode)

    ≤ 97%

    Transfer time

    mains ↔ battery: 0 ms; mains ↔ bypass: 4 ms; ECO ↔ inverter: 10 ms

    Cold start

    cold start, soft start

    Frequency converter mode

    yes (CVCF)

    EPO connector

    yes

    Protections

    short-circuit, overvoltage, overload, overtemperature

    Alarms

    overload, battery mode, low battery, fan failure

    Parallel operation

    no

    Cooling

    active, PWM-controlled

    EMC

    PN-EN IEC 62040-2, C2

    COMMUNICATION
    Control panel

    rotatable (90°) LCD display, 4 LEDs, 5 buttons

    Menu languages

    8, including Polish

    Communication ports

    USB (HID) / RS232 (DB9) / dry contacts / RJ45 (IoT) / Intelligent Slot

    Optional cards

    Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts, WiFi

    Protocols (with card)

    HTTP(S), SNMP, Modbus RTU/TCP, MQTT, SSH, NTP, SMTP, Syslog, RADIUS, LDAP, 802.1X

    Operating systems

    MS Windows / Linux / Unix / MacOS, VMware ESXi, Hyper-V

    ENCLOSURE AND ENVIRONMENT
    Dimensions (W x H x D)

    438 x 85.5 (2U) x 600 mm

    Weight with batteries

    23.3 kg

    Ingress protection

    IP20

    Colour

    black

    Operating temperature

    0–40 °C

    Humidity

    0–95% (non-condensing)

    Operating altitude

    up to 1000 m a.s.l. without derating; 1000–3000 m: -1% per 100 m

    Noise level (1 m)

    < 50 dB

    * Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.

    GT S 11 IoT 2kVA UPS – overview

    GT S 11 IoT 2kVA is an on-line double-conversion UPS (VFI-SS-313) with an output power factor of 1, so real power equals apparent power: 2000 W. The load is permanently supplied by the inverter and transfer to battery is seamless (0 ms). Efficiency reaches 97% in ECO mode.

    The RJ45 (IoT) port and Intelligent Slot cards integrate the UPS with BMS, DCIM, SCADA and SIEM systems (incl. SNMP, Modbus TCP, MQTT). The rotatable LCD supports 8 languages. Batteries are replaced from the front without powering down the load.

    Frequently asked questions

    How does an on-line UPS differ from a line-interactive UPS?

    An on-line UPS continuously generates the output voltage in its inverter, so the load is isolated from outages and mains disturbances (0 ms transfer). A line-interactive UPS switches to battery only after detecting a failure, within a few milliseconds.

    How can I extend the backup time of the GT S 11 2kVA?

    You can connect external battery modules (EBM, 72 V DC); the UPS detects them automatically. Estimate runtime for your load in the UPS calculator.

    Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.

    Back panel