Power |
10kVA / 10kW |
INPUT | |
Voltage rate | 190 ~ 304 VAC (linear reduction between 50% and 100% load); 304 ~ 499 VAC (without lowering) |
Frequency rate | 40-70 Hz |
tdDi |
≤5% |
Input connector |
Terminal block |
Wiring | Three-phase five-wire (3Φ + N + PE) / Single-phase Three-wire (1Φ + N + PE) |
OUTPUT | |
Voltage |
208 V (PF = 0,9)/220/230/240 Vac |
Frequency (bat. mode) | Synchronised to By-pass in network mode; 50/60 Hz ± 0,1% Hz in battery mode |
Power factor (PF) |
1 |
Peak factor |
3:1 |
Waveform |
Sinusoidal |
Output connectors |
Terminal block |
Wiring | Single-phase Three-wire (1Φ + N + PE) |
EFFICIENCY | |
Online mode |
95% |
Eco mode |
98% |
BATTERY | |
Backup time* | Battery cabinet required |
Number of batteries in string |
16 pcs (16 ~ 20 configurable) |
|
|
TRANSFER TIME | |
line ↔ battery |
0ms |
inverter ↔ bypass |
0ms |
inverter → eco |
1ms |
eco → inverter |
<10ms |
INTERFACE | |
Display |
LCD |
Communication ports | RS323, USB, RS485, SNMP |
Slot for expansion cards |
AS400, relay card, SNMP |
Software | Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 / ESX: HyperV |
PHISICAL | |
Dimensions (mm) |
440 x 660 x 176 |
Weight with batteries |
67kg |
OTHER | |
Noise level |
≤ 58 dB |
Operating temperature |
0°C – 40°C |
Audiable alarms |
Yes |
For you calculation needs please contact our Sales Department. We’ve made an effort to provide correct technical data in this publication but we recommend to contact our Sales Department in case of any doubts before making your purchase decisions. Any errors in the description do not constitute grounds for a claim.