UPS GT SM 33 30kVA/30kW On-Line 3F/3F Tower
- Power 30 kVA / 30 kW
- Power factor (PF) 1
| Power | 30 kVA / 30 kW |
| Topology (IEC 62040-3) | On-line double conversion (VFI) |
| Form factor | free-standing Tower |
| INPUT | |
| Phases | 3 |
| Nominal voltage | 380 / 400 / 415 V |
| Voltage range | 304–485 V |
| Nominal frequency | 50 / 60 Hz (auto-sensing) |
| Frequency range | 40–70 Hz |
| Input power factor | ≥ 0.99 |
| Current distortion (THDi) | < 3% |
| Input connection | 3P + N + PE (terminal block) |
| BYPASS | |
| Bypass | separate bypass input |
| Bypass voltage range | -20% / +15% |
| Input connection | 3P + N (terminal block) |
| OUTPUT | |
| Phases | 3 |
| Output voltage | 380 / 400 / 415 V (configurable) |
| Voltage accuracy | ±1% |
| Output frequency | 50 / 60 Hz ±0.1% (battery mode) |
| Power factor (PF) | 1 |
| Crest factor (CF) | 3:1 |
| Voltage distortion (THDu) | ≤ 1% (linear load), ≤ 4% (non-linear) |
| Overload capacity | < 110%: transfer to bypass after 60 min; 110–125%: transfer to bypass after 10 min; 125–150%: transfer to bypass after 1 min; > 150%: transfer to bypass after 200 ms |
| Output connection | 3P + N + PE (terminal block) |
| BATTERIES | |
| Battery technology | VRLA / AGM |
| Battery voltage | 240 V DC (configurable 180–276 V DC) |
| Internal batteries | 80 x 12 V / 7–10 Ah internal (2 x 40) or external EBM/STB |
| External battery modules (EBM) | yes – EBM cabinets or STB racks |
| Charging current | 12 A |
| EFFICIENCY AND FUNCTIONS | |
| Efficiency | ≥ 96% |
| Efficiency (ECO mode) | ≥ 99% |
| Transfer time | synchronised transfer: 0 ms |
| Frequency converter mode | yes (CVCF) |
| EPO connector | yes |
| Protections | short-circuit, overload, overtemperature |
| Alarms | overload, battery mode, low battery, fan failure |
| Parallel operation | up to 4 units |
| EMC | PN-EN IEC 62040-2 |
| COMMUNICATION | |
| Control panel | LED + 5" LCD touch screen |
| Menu languages | Polish, English |
| Communication ports | USB / RS232 / RS485 / dry contacts / 2 x Intelligent Slot |
| Optional cards | Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts |
| ENCLOSURE AND ENVIRONMENT | |
| Dimensions (W x H x D) | 360 x 950 x 850 mm |
| Weight without batteries | 93 kg |
| Ingress protection | IP20 |
| Colour | black |
| Operating temperature | 0–40 °C |
| Humidity | 0–95% (non-condensing) |
| Operating altitude | up to 1000 m a.s.l. without derating; 1000–3000 m with derating |
| Noise level (1 m) | ≤ 65 dB |
GT SM 33 30kVA is a three-phase on-line double-conversion UPS with unity power factor. The series has been discontinued; we continue to service and inspect installed units.
The series has been discontinued. We provide service for installed units, and our Sales Department will recommend a current equivalent.
Technical data according to the GT UPS datasheet (version 01.23). Please consult our Sales Department before ordering.