UPS GT S 33 Pro Tower 40kVA/40kW On-Line 3F/3F

  • Power 40 kVA / 40 kW
  • Waveform sine wave
  • Power factor (PF) 1

Request a quote Specifications

UPS GT S 33 Pro Tower 40kVA/40kW On-Line 3F/3F

GT S 33 Pro Tower 40kVA/40kW UPS – a three-phase on-line double-conversion UPS (3/3) for server rooms, data centers, hospitals and industrial plants.

  • On-line VFI, PF 1, up to 96% efficiency (99% in ECO mode)
  • Up to 4 units in parallel, separate bypass input
  • Internal batteries: 40 or 80 blocks*
  • VRLA/AGM, NiCd or lithium-ion batteries
  • 5" touch screen, 2 hot-swap communication slots

Size your UPS in the calculator or request a quote.

Zapytanie

Technical specifications

Power

40 kVA / 40 kW

Topology (IEC 62040-3)

On-line double conversion (VFI-SS-111)

Form factor

free-standing Tower

INPUT
Phases

3

Nominal voltage

380 / 400 / 415 V

Voltage range

110–498 V

Nominal frequency

50 / 60 Hz (auto-sensing)

Frequency range

40–72 Hz

Input power factor

≥ 0.99

Current distortion (THDi)

≤ 3%

Input connection

3P + N + PE (terminal block)

Earthing system

TN-S / TN-C / TN-C-S / TT

BYPASS
Bypass

separate bypass input

Bypass voltage range

187–498 V

Input connection

3P + N (terminal block)

OUTPUT
Phases

3

Output voltage

380 / 400 / 415 V (configurable)

Voltage accuracy

±1% (balanced load), ±2% (unbalanced load)

Output frequency

50 / 60 Hz ±0.1% (battery mode)

Waveform

sine wave

Power factor (PF)

1

Crest factor (CF)

3:1

Voltage distortion (THDu)

≤ 1%

Overload capacity

102–110%: transfer to bypass after 60 min; 111–125%: transfer to bypass after 10 min; 126–150%: transfer to bypass after 60 s; > 151%: transfer to bypass after 0.2 s

Output connection

3P + N + PE (terminal block)

BATTERIES
Battery technology

VRLA / AGM / NiCd / Li-ion

Battery voltage

480 V DC (VRLA/AGM), range 313–607 V DC

Internal batteries

80 x 12 V / 7–10 Ah (VRLA/AGM)

Backup time*

≈ 7 min (80 x 9 Ah)

Compatible EBM

GTS33BP140-1409

Backup time with 1 EBM*

≈ 27 min

Charging current

40 A

EFFICIENCY AND FUNCTIONS
Efficiency

≤ 96%

Efficiency (ECO mode)

≤ 99%

Transfer time

synchronised transfer: 0 ms

Cold start

cold start, soft start

Frequency converter mode

yes (CVCF)

EPO connector

yes

Protections

short-circuit, overvoltage, overload, overtemperature

Alarms

overload, bypass mode, battery mode, low battery, fan failure

Parallel operation

up to 4 units

EMC

PN-EN IEC 62040-2

COMMUNICATION
Control panel

LED + 5" LCD touch screen

Menu languages

10, including Polish

Communication ports

USB / RS232 (DB9) / dry contacts / 2 x Intelligent Slot (hot-swap)

Optional cards

Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts

ENCLOSURE AND ENVIRONMENT
Dimensions (W x H x D)

500 x 860 x 887 mm

Weight without batteries

139 kg

Weight with batteries

331 kg (80 pcs)

Ingress protection

IP20

Colour

black

Operating temperature

0–40 °C

Humidity

5–95% (non-condensing)

Operating altitude

up to 1500 m a.s.l. without derating

Noise level (1 m)

≤ 55 dB

* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.

GT S 33 Pro Tower 40kVA UPS – overview

GT S 33 Pro Tower 40kVA is a three-phase on-line double-conversion UPS (VFI-SS-111) with unity power factor, delivering 40 kW of real power. It has separate rectifier and bypass inputs, supports VRLA/AGM, NiCd and lithium-ion batteries and can operate as a frequency converter.

Up to four units can be paralleled for more power or N+1 redundancy. Up to 99% efficiency in ECO mode reduces energy and cooling costs.

Frequently asked questions

What backup time does the GT S 33 Pro Tower 40kVA provide?

With the GTS33BP140-1409 battery module approx. 27 min at 75% load. Runtime can be extended with additional battery cabinets – contact us for a configuration.

Does GT S 33 Pro support lithium-ion batteries?

Yes. The UPS supports VRLA/AGM, NiCd and lithium-ion batteries.

Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.

Back panel

To download

  • KK_GT_UPS_S_33_Pro_T_40kVA_03.24.pdf