UPS GT S FLEXI IoT 10kVA/10kW On-Line 3F/3F, 3F/1F, 1F/1F Rack/Tower
- Power 10 kVA / 10 kW
- Waveform sine wave
- Power factor (PF) 1
| Power | 10 kVA / 10 kW |
| Topology (IEC 62040-3) | On-line double conversion (VFI-SS-111) |
| Form factor | Rack 19" 3U / Tower (convertible) |
| Phase configuration | 3F/3F, 3F/1F, 1F/1F |
| INPUT | |
| Phases | 3 or 1 |
| Nominal voltage | 380 / 400 / 415 V or 220 / 230 / 240 V |
| Voltage range | 273–520 V (3-ph) or 160–300 V (1-ph) |
| Nominal frequency | 50 / 60 Hz (auto-sensing) |
| Frequency range | 40–70 Hz |
| Input power factor | ≥ 0.995 |
| Current distortion (THDi) | ≤ 3% |
| Input connection | 3P + N + PE or 1P + N + PE (terminal block) |
| Earthing system | TN-S / TN-C / TN-C-S / TT |
| BYPASS | |
| Bypass | separate bypass input |
| Bypass voltage range | -40% / +25% |
| OUTPUT | |
| Output voltage | 380 / 400 / 415 V or 220 / 230 / 240 V (configurable) |
| Voltage accuracy | ±1% |
| Output frequency | 50 / 60 Hz ±0.1% (battery mode) |
| Waveform | sine wave |
| Power factor (PF) | 1 |
| Crest factor (CF) | 3:1 |
| Voltage distortion (THDu) | ≤ 1% |
| Overload capacity | 100–105%: continuous; 105–125%: transfer to bypass after 10 min; 125–150%: transfer to bypass after 1 min; > 150%: transfer to bypass after 500 ms |
| Output connection | 3P + N + PE or 1P + N + PE (terminal block) |
| BATTERIES | |
| Battery technology | VRLA / AGM / Li-ion |
| Battery voltage | 240 V DC (192 / 216 / 240 V DC) |
| Internal batteries | none – external EBM/STB only |
| Compatible EBM | GTEBM_RT3_240V_YA4YU |
| Backup time with 1 EBM* | ≈ 7 min |
| Backup time with 2 EBM* | ≈ 17 min |
| Backup time with 3 EBM* | ≈ 30 min |
| Charging current | 13 A |
| EFFICIENCY AND FUNCTIONS | |
| Efficiency | ≤ 95% |
| Efficiency (ECO mode) | ≤ 98% |
| Transfer time | synchronised transfer: 0 ms |
| Cold start | soft start |
| Frequency converter mode | yes (CVCF) |
| EPO connector | yes |
| Protections | short-circuit, overload, overtemperature |
| Alarms | overload, battery mode, low battery, fan failure |
| Parallel operation | up to 3 units |
| EMC | PN-EN IEC 62040-2, C3 |
| COMMUNICATION | |
| Control panel | LCD touch screen |
| Menu languages | 10, including Polish |
| Communication ports | USB (HID) / RS232 / dry contacts / RJ45 / Intelligent Slot |
| Optional cards | Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts |
| ENCLOSURE AND ENVIRONMENT | |
| Dimensions (W x H x D) | 438 x 129 (3U) x 590 mm |
| Weight without batteries | 15.5 kg |
| Ingress protection | IP20 |
| Colour | black |
| Operating temperature | 0–50 °C |
| Humidity | 0–95% (non-condensing) |
| Operating altitude | up to 1000 m a.s.l. without derating |
| Noise level (1 m) | ≤ 55 dB |
* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.
GT S FLEXI IoT 10kVA is an on-line double-conversion UPS (VFI-SS-111) with configurable topology: three-phase in/out, three-phase in with single-phase out, or single-phase. This simplifies installation planning and reduces the number of models to stock.
The UPS works with external battery sets only (EBM/STB), including lithium-ion. It has a separate bypass input, can operate as a frequency converter and supports up to 3 units in parallel.
Yes, in 3/1 configuration the UPS draws power from three phases and outputs a single 220/230/240 V phase.
Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.