UPS GT M 1000VA/900W ECO Line-Interactive 1F Rack/Tower
- Power 1000 VA / 900 W
- Waveform pure sine wave
- Power factor (PF) 0.9
2.png
9.png
11.png
| Power | 1000 VA / 900 W |
| Topology (IEC 62040-3) | Line-interactive (VI) |
| Form factor | Rack 19" / Tower, 2U |
| INPUT | |
| Phases | 1 |
| Nominal voltage | 220 / 230 / 240 V |
| Voltage range | 154–288 V |
| Nominal frequency | 50 / 60 Hz |
| Frequency range | 45–65 Hz |
| Input connection | IEC 60320 C14 (10 A) |
| Earthing system | TN-S / TN-C / TN-C-S / TT |
| OUTPUT | |
| Output voltage | 220 / 230 / 240 V |
| Voltage regulation | AVR |
| Voltage accuracy (line mode) | -10% / +6% |
| Voltage accuracy (battery mode) | ±5% |
| Output frequency | 50 / 60 Hz ±0.1 Hz (battery mode) |
| Waveform | pure sine wave |
| Power factor (PF) | 0.9 |
| Crest factor (CF) | 3:1 |
| Voltage distortion (THDu) | ≤ 10% |
| Overload capacity (line mode) | 110–119%: shutdown after 3 min; 150–165%: shutdown after 200 ms |
| Overload capacity (battery mode) | 103–117%: shutdown after 30 s; 118–127%: shutdown after 100 ms |
| Output sockets | 4 x IEC 60320 C13 |
| BATTERIES | |
| Battery technology | VRLA / AGM |
| Internal batteries | 2 x 12 V / 9 Ah |
| Battery voltage | 24 V DC |
| Backup time* | ≈ 5 min |
| External battery modules (EBM) | no |
| Charging current | 1.1 A |
| Recharge time | approx. 3 h to 90% capacity |
| EFFICIENCY AND FUNCTIONS | |
| Efficiency | ≤ 97% |
| Efficiency (AVR mode) | ≤ 92% (boost) / ≤ 95% (buck) |
| Efficiency (battery mode) | ≤ 80% |
| Transfer time | 2–4 ms (typical) |
| Cold start | yes |
| EPO connector | no |
| Protections | short-circuit, overvoltage, overload, overtemperature |
| Alarms | overload, battery mode, low battery, fan failure |
| Data line surge protection | RJ11 / RJ45 |
| EMC | PN-EN IEC 62040-2, C1 |
| COMMUNICATION | |
| Control panel | rotatable (90°) LCD display |
| Communication ports | USB (HID) / RS232 |
| Operating systems | MS Windows / Linux / Unix / MacOS |
| ENCLOSURE AND ENVIRONMENT | |
| Dimensions (W x H x D) | 438 x 86.5 (2U) x 436 mm |
| Weight with batteries | 14 kg |
| Ingress protection | IP20 |
| Colour | black |
| Operating temperature | 0–40 °C |
| Humidity | 0–95% (non-condensing) |
| Noise level (1 m) | < 45 dB |
* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.
GT M 1000VA ECO is a line-interactive (VI) UPS with automatic voltage regulation (AVR) and pure sine wave output. The universal 2U enclosure can be installed in a 19" rack or stand upright as a tower, and the rotatable (90°) LCD display is readable in both positions.
The GT M series is designed for network cabinets, small server rooms, CCTV systems, PBX systems and workstations with active PFC power supplies. It can operate with a generator set.
At 75% load approx. 5 min on internal batteries. This version does not support external battery modules.
This version has USB and RS232 ports without a network card slot. For network monitoring choose the standard GT M version with an Intelligent Slot.
Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.