GT UPS
  • Polski
  • Українська

UPS GT M 2000VA/1800W Line-Interactive 1F Rack/Tower

  • Power 2000 VA / 1800 W
  • Waveform pure sine wave
  • Power factor (PF) 0.9

Request a quote Specifications

UPS GT M 2000VA/1800W Line-Interactive 1F Rack/Tower

GT M 2000VA/1800W UPS – a line-interactive UPS with pure sine wave output for 19" rack (2U) or tower installation. Protects servers, switches, NAS and workstations.

  • Pure sine wave, PF 0.9 and AVR
  • Approx. 6 min backup time*, up to approx. 84 min with 3 EBMs
  • Sockets: 8 x IEC C13
  • USB (HID), RS232, SNMP/Modbus card slot
  • Rotatable LCD display, EPO connector

Size your UPS in the calculator or request a quote.

Buy from B2B

Preferred for power supply

  • 2.png

  • 9.png

  • 11.png

Zapytanie

Technical specifications

Power

2000 VA / 1800 W

Topology (IEC 62040-3)

Line-interactive (VI)

Form factor

Rack 19" / Tower, 2U

INPUT
Phases

1

Nominal voltage

220 / 230 / 240 V

Voltage range

154–288 V

Nominal frequency

50 / 60 Hz

Frequency range

45–65 Hz

Input connection

IEC 60320 C14 (10 A)

Earthing system

TN-S / TN-C / TN-C-S / TT

OUTPUT
Output voltage

220 / 230 / 240 V

Voltage regulation

AVR

Voltage accuracy (line mode)

-10% / +6%

Voltage accuracy (battery mode)

±5%

Output frequency

50 / 60 Hz ±0.1 Hz (battery mode)

Waveform

pure sine wave

Power factor (PF)

0.9

Crest factor (CF)

3:1

Voltage distortion (THDu)

≤ 3%

Overload capacity (line mode)

110–119%: shutdown after 3 min; 150–165%: shutdown after 200 ms

Overload capacity (battery mode)

103–117%: shutdown after 30 s; 118–127%: shutdown after 100 ms

Output sockets

8 x IEC 60320 C13

BATTERIES
Battery technology

VRLA / AGM

Internal batteries

4 x 12 V / 7 Ah

Battery voltage

48 V DC

Backup time*

≈ 6 min

External battery modules (EBM)

yes (optional)

Compatible EBM

UPSGTBP48VRT89

Backup time with 1 EBM*

≈ 29 min

Backup time with 2 EBM*

≈ 53 min

Backup time with 3 EBM*

≈ 84 min

Charging current

1.5 A

Recharge time

approx. 3 h to 90% capacity

EFFICIENCY AND FUNCTIONS
Efficiency

≤ 97%

Efficiency (AVR mode)

≤ 92% (boost) / ≤ 95% (buck)

Efficiency (battery mode)

≤ 80%

Transfer time

2–4 ms (typical)

Cold start

yes

EPO connector

yes

Protections

short-circuit, overvoltage, overload, overtemperature

Alarms

overload, battery mode, low battery, fan failure

Data line surge protection

RJ11 / RJ45

EMC

PN-EN IEC 62040-2, C1

COMMUNICATION
Control panel

rotatable (90°) LCD display

Communication ports

USB (HID) / RS232 / Intelligent Slot

Optional cards

Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts

Operating systems

MS Windows / Linux / Unix / MacOS

ENCLOSURE AND ENVIRONMENT
Dimensions (W x H x D)

438 x 86.5 (2U) x 436 mm

Weight with batteries

27 kg

Ingress protection

IP20

Colour

black

Operating temperature

0–40 °C

Humidity

0–95% (non-condensing)

Noise level (1 m)

< 45 dB

* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.

GT M 2000VA UPS – overview

GT M 2000VA is a line-interactive (VI) UPS with automatic voltage regulation (AVR) and pure sine wave output. The universal 2U enclosure can be installed in a 19" rack or stand upright as a tower, and the rotatable (90°) LCD display is readable in both positions.

The GT M series is designed for network cabinets, small server rooms, CCTV systems, PBX systems and workstations with active PFC power supplies. It can operate with a generator set.

Frequently asked questions

What backup time does the GT M 2000VA UPS provide?

At 75% load approx. 6 min on internal batteries. With EBMs (UPSGTBP48VRT89): approx. 29 min with 1 module, 53 min with 2 and 84 min with 3 modules.

Can the GT M be monitored over the network?

Yes, with an optional SNMP/WEB card installed in the Intelligent Slot. Modbus and dry-contact cards are also available. See UPS software.

Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.

In the box

To download

Ustawienia cookies