UPS GT COMBO 3/1 10kVA/9kW On-Line 3F/1F Tower
- Power 10 kVA / 9 kW
- Waveform sine wave
- Power factor (PF) 0.9
| Power | 10 kVA / 9 kW |
| Topology (IEC 62040-3) | On-line double conversion (VFI) |
| Form factor | free-standing Tower |
| INPUT | |
| Phases | 3 or 1 |
| Nominal voltage | 380 / 400 / 415 V or 220 / 230 / 240 V |
| Voltage range | 190–478 V (3-ph) or 110–276 V (1-ph) |
| Nominal frequency | 50 / 60 Hz (auto-sensing) |
| Frequency range | 40–70 Hz |
| Input power factor | ≥ 0.99 |
| Current distortion (THDi) | ≤ 5% |
| Input connection | 3P + N + PE or 1P + N + PE (terminal block) |
| OUTPUT | |
| Phases | 1 |
| Output voltage | 200 / 208 / 220 / 230 / 240 V (configurable) |
| Voltage accuracy | ±1% |
| Output frequency | 50 / 60 Hz ±0.1% (battery mode) |
| Waveform | sine wave |
| Power factor (PF) | 0.9 |
| Crest factor (CF) | 3:1 |
| Voltage distortion (THDu) | ≤ 2% (linear load), ≤ 5% (non-linear) |
| Overload capacity | 100–110%: transfer to bypass after 5 min; 110–130%: transfer to bypass after 1 min; 130–150%: transfer to bypass after 10 s; > 150%: transfer to bypass after 2 s |
| Output connection | 1P + N + PE (terminal block) |
| BATTERIES | |
| Battery technology | VRLA / AGM |
| Battery voltage | 288 V DC |
| Internal batteries | 24 or 48 x 12 V / 9 Ah |
| Backup time* | ≈ 8 min (24 pcs) / ≈ 21 min (48 pcs), rated load |
| External battery modules (EBM) | yes (optional) |
| Charging current | 4 A |
| Recharge time | approx. 3 h to 90% capacity |
| EFFICIENCY AND FUNCTIONS | |
| Efficiency | ≥ 94% |
| Efficiency (ECO mode) | ≥ 98% |
| Transfer time | synchronised transfer: 0 ms |
| EPO connector | yes |
| Protections | short-circuit, overload, overtemperature |
| Alarms | overload, battery mode, low battery, fan failure |
| Parallel operation | up to 4 units |
| EMC | PN-EN IEC 62040-2 |
| COMMUNICATION | |
| Control panel | LCD display |
| Communication ports | USB / RS232 / Intelligent Slot |
| Optional cards | Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts |
| ENCLOSURE AND ENVIRONMENT | |
| Dimensions (W x H x D) | 350 x 890 x 650 mm |
| Weight without batteries | 74.3 kg |
| Ingress protection | IP20 |
| Colour | black |
| Operating temperature | 0–40 °C |
| Humidity | 0–95% (non-condensing) |
| Operating altitude | up to 1000 m a.s.l. without derating; 1000–3000 m with derating |
| Noise level (1 m) | ≤ 58 dB |
GT COMBO 3/1 10kVA is an on-line double-conversion UPS that can be fed from a three-phase or single-phase mains and supplies single-phase voltage. Batteries are built into the tower enclosure.
GT S FLEXI IoT with configurable phases is the successor in this range.
The series has been discontinued. We provide service for installed units, and our Sales Department will recommend a current equivalent.
Technical data according to the GT UPS datasheet (version 02.23). Please consult our Sales Department before ordering.