GT UPS
  • Polski
  • Українська

UPS GT COMBO 3/1 10kVA/9kW On-Line 3F/1F Tower

  • Power 10 kVA / 9 kW
  • Waveform sine wave
  • Power factor (PF) 0.9

Request a quote Specifications

11.png

UPS GT COMBO 3/1 10kVA/9kW On-Line 3F/1F Tower

GT COMBO 3/1 10kVA/9kW UPS – an on-line UPS with three- or single-phase input, single-phase output and built-in batteries. Archive model – we provide service and will recommend a successor.

  • On-line VFI, 0 ms transfer time
  • 3-phase or 1-phase input, 1-phase output
  • Internal 9 Ah batteries, expandable with EBMs
  • Up to 4 units in parallel

Size your UPS in the calculator or request a quote.

222.png

UPS GT COMBO 3/1 10kVA/9kW On-Line 3F/1F Tower

GT COMBO 3/1 10kVA/9kW UPS – an on-line UPS with three- or single-phase input, single-phase output and built-in batteries. Archive model – we provide service and will recommend a successor.

  • On-line VFI, 0 ms transfer time
  • 3-phase or 1-phase input, 1-phase output
  • Internal 9 Ah batteries, expandable with EBMs
  • Up to 4 units in parallel

Size your UPS in the calculator or request a quote.

    Zapytanie

    Technical specifications

    Power

    10 kVA / 9 kW

    Topology (IEC 62040-3)

    On-line double conversion (VFI)

    Form factor

    free-standing Tower

    INPUT
    Phases

    3 or 1

    Nominal voltage

    380 / 400 / 415 V or 220 / 230 / 240 V

    Voltage range

    190–478 V (3-ph) or 110–276 V (1-ph)

    Nominal frequency

    50 / 60 Hz (auto-sensing)

    Frequency range

    40–70 Hz

    Input power factor

    ≥ 0.99

    Current distortion (THDi)

    ≤ 5%

    Input connection

    3P + N + PE or 1P + N + PE (terminal block)

    OUTPUT
    Phases

    1

    Output voltage

    200 / 208 / 220 / 230 / 240 V (configurable)

    Voltage accuracy

    ±1%

    Output frequency

    50 / 60 Hz ±0.1% (battery mode)

    Waveform

    sine wave

    Power factor (PF)

    0.9

    Crest factor (CF)

    3:1

    Voltage distortion (THDu)

    ≤ 2% (linear load), ≤ 5% (non-linear)

    Overload capacity

    100–110%: transfer to bypass after 5 min; 110–130%: transfer to bypass after 1 min; 130–150%: transfer to bypass after 10 s; > 150%: transfer to bypass after 2 s

    Output connection

    1P + N + PE (terminal block)

    BATTERIES
    Battery technology

    VRLA / AGM

    Battery voltage

    288 V DC

    Internal batteries

    24 or 48 x 12 V / 9 Ah

    Backup time*

    ≈ 8 min (24 pcs) / ≈ 21 min (48 pcs), rated load

    External battery modules (EBM)

    yes (optional)

    Charging current

    4 A

    Recharge time

    approx. 3 h to 90% capacity

    EFFICIENCY AND FUNCTIONS
    Efficiency

    ≥ 94%

    Efficiency (ECO mode)

    ≥ 98%

    Transfer time

    synchronised transfer: 0 ms

    EPO connector

    yes

    Protections

    short-circuit, overload, overtemperature

    Alarms

    overload, battery mode, low battery, fan failure

    Parallel operation

    up to 4 units

    EMC

    PN-EN IEC 62040-2

    COMMUNICATION
    Control panel

    LCD display

    Communication ports

    USB / RS232 / Intelligent Slot

    Optional cards

    Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts

    ENCLOSURE AND ENVIRONMENT
    Dimensions (W x H x D)

    350 x 890 x 650 mm

    Weight without batteries

    74.3 kg

    Ingress protection

    IP20

    Colour

    black

    Operating temperature

    0–40 °C

    Humidity

    0–95% (non-condensing)

    Operating altitude

    up to 1000 m a.s.l. without derating; 1000–3000 m with derating

    Noise level (1 m)

    ≤ 58 dB

    GT COMBO 3/1 10kVA UPS – overview

    GT COMBO 3/1 10kVA is an on-line double-conversion UPS that can be fed from a three-phase or single-phase mains and supplies single-phase voltage. Batteries are built into the tower enclosure.

    GT S FLEXI IoT with configurable phases is the successor in this range.

    Frequently asked questions

    Is this model still available?

    The series has been discontinued. We provide service for installed units, and our Sales Department will recommend a current equivalent.

    Technical data according to the GT UPS datasheet (version 02.23). Please consult our Sales Department before ordering.