GT UPS
  • Polski
  • Українська

UPS GT S 33 Rack/Tower 15kVA/15kW On-Line 3F/3F

  • Power 15 kVA / 15 kW
  • Waveform sine wave
  • Power factor (PF) 1

Request a quote Specifications

UPS GT S 33 Rack/Tower 15kVA/15kW On-Line 3F/3F

GT S 33 Rack/Tower 15kVA/15kW UPS – a three-phase on-line UPS (3/3) in a 3U enclosure for 19" racks or tower use. For server rooms and ICT cabinets with three-phase supply.

  • On-line VFI, PF 1, up to 95% efficiency (98% in ECO)
  • Only 3U high
  • EBMs: up to approx. 26 min*
  • Up to 4 units in parallel, separate bypass
  • 5" touch screen, USB, RS232, RS485, SNMP/Modbus slot

Size your UPS in the calculator or request a quote.

Zapytanie

Technical specifications

Power

15 kVA / 15 kW

Topology (IEC 62040-3)

On-line double conversion (VFI-SS-111)

Form factor

Rack 19" 3U / Tower

INPUT
Phases

3

Nominal voltage

380 / 400 / 415 V

Voltage range

304–478 V

Rated current

29 A

Nominal frequency

50 / 60 Hz (auto-sensing)

Frequency range

40–70 Hz

Input power factor

≥ 0.99

Current distortion (THDi)

< 3%

Input connection

3P + N + PE (terminal block)

Earthing system

TN-S / TN-C / TN-C-S / TT

BYPASS
Bypass

separate bypass input

Bypass voltage range

-20% / +15%

Frequency range

±1 / ±3 / ±5 Hz

OUTPUT
Phases

3

Output voltage

380 / 400 / 415 V (configurable)

Output current

23 A

Voltage accuracy

±1%

Output frequency

50 / 60 Hz ±0.1 Hz (battery mode)

Waveform

sine wave

Power factor (PF)

1

Crest factor (CF)

3:1

Voltage distortion (THDu)

≤ 1%

Overload capacity

101–110%: transfer to bypass after 60 min; 110–125%: transfer to bypass after 10 min; 125–150%: transfer to bypass after 1 min; > 150%: transfer to bypass after 0.2 s

Output connection

3P + N + PE (terminal block)

BATTERIES
Battery technology

VRLA / AGM

Battery voltage

240 V DC (192 / 216 V DC)

Internal batteries

none – external EBM/STB only

Compatible EBM

UPSGTS31EMBRT 209

Backup time with 2 EBM*

≈ 11 min

Backup time with 4 EBM*

≈ 26 min

Charging current

10 A

EFFICIENCY AND FUNCTIONS
Efficiency

≤ 95%

Efficiency (ECO mode)

≤ 98%

Transfer time

synchronised transfer: 0 ms

Frequency converter mode

yes (CVCF)

EPO connector

yes

Protections

short-circuit, overload, overtemperature

Alarms

overload, battery mode, low battery, fan failure

Parallel operation

up to 4 units

EMC

PN-EN IEC 62040-2, C3

COMMUNICATION
Control panel

LED + 5" LCD touch screen

Menu languages

Polish, English

Communication ports

USB / RS232 / RS485 / dry contacts / Intelligent Slot

Optional cards

Intelligent Slot cards: WEB/SNMP, RS485, MODBUS, dry contacts

ENCLOSURE AND ENVIRONMENT
Dimensions (W x H x D)

440 x 130 (3U) x 660 mm

Weight without batteries

24 kg

Ingress protection

IP20

Colour

black RAL 7021

Operating temperature

0–40 °C

Humidity

0–95% (non-condensing)

Noise level (1 m)

< 60 dB

* Backup time at 75% load and PF=0.8. Actual runtime depends on load, temperature and battery condition.

GT S 33 Rack/Tower 15kVA UPS – overview

GT S 33 15kVA is a three-phase on-line double-conversion UPS (VFI-SS-111) rated 15 kVA / 15 kW in a 19" 3U rack / tower enclosure. It has a separate bypass input, a 5" touch screen with Polish and English menus and can operate as a frequency converter (CVCF).

It is intended for server rooms, automation systems, medical and industrial sites with three-phase supply. Paralleling several units increases capacity or provides N+1 redundancy.

Frequently asked questions

How to get longer backup time for GT S 33 15kVA?

The UPS works with UPSGTS31EMBRT 209 external battery modules or STB cabinets. Example runtimes are in the specification table; our Sales Department will size the configuration.

Technical data according to the GT UPS datasheet (version 01.26). Please consult our Sales Department before ordering.

Back panel

To download

  • KK_GT_UPS_S_33_RT_15kVA_02.23.pdf

  • DZ_UPS GT S 33 RT 15kVA_02.23.pdf

  • IO_GT_UPS_S_33_RT_10-30kVA_01.23.pdf

Ustawienia cookies